Loading...
Pathfinder C1

Operating Specifications


Input voltage : 190V~265V AC
Battery : Self-contained Ni Cd Battery
Battery backup : 3 hours
Color temperatures : 6000 K
Frequency : 50/60 Hz
Optics : Acrylic Diffuser
Average luminance(White) : ≥500 cd/m2
Uniformity : ≥0.2

 

Indication of Battery and Self Diagnostics Status


Function test Weekly 5 minutes test duration
Duration test The 522nd function test is a duration of 3 hours
Green Continuously Mains available, Charging OK
Off No mains available or emergency mode
Red Flashing (1 Hz) Lamp source faulty
Red continuously Battery failure
Red / Green alternating Test mode

 

Essential Features

  • Ingress protection 20
  • Standard automatic self test
  • Suitable for mounting on either a ceiling or a wall by simply changing the end caps
  • Safety standard : EN 60598
  • Emergency lighting standard : EN 1838 / CIE S 020 (2007)
    • Electromagnetic compatibility EMC Standard
    • EN 61547 for EMC immunity
    • EN 55015 for disturbance measurement
  • Electromagnetic compatibility is essential to prevent electromagnetic eterference which disturbs the operation of Mobile Phones, Pacemakers, internet operation and can cause data loss.

 

Product
Code
Product
Name
Size (mm)
L x B x H
Input Power Viewing Distance (m) Weight
(Kg)
EXC1 - 006 Pathfinder C1 275 x 82.5 x 211 6 Watts 24 0.85